Supported Lineup

* You can scroll this table sideways.

Item MELSOFT MX OPC Server DA / UA Model DeviceXPlorer OPC Server Model
MX OPC Server DA SW7DND-OPCDAS-E

DXPV7PR-HW
DXPV7PR-SW
DXPV7ML-HW
DXPV7ML-SW
DXPV7SG-HW
DXPV7SG-SW

SW7DND-OPCDAS-EA
SW7DND-OPCDAS-EAZ
MX OPC Server UA SW3DND-OPCUAS-E
SW3DND-OPCUAS-EA
SW3DND-OPCUAS-EAZ

DeviceXPlorer OPC Server Lineup Explanation

* You can scroll this table sideways.

Model Edition Professional Functions *1 Accessible Machines
DXPV7PR-HW
DXPV7PR-SW
Professional Supported All Machines
DXPV7ML-HW
DXPV7ML-SW
Multi Not Supported All Machines
DXPV7SG-HW
DXPV7SG-SW
Single Not Supported  1 Series

*1 Includes Cloud functions (MQTT/HTTP) and OPC UA Historical Access / Alarms & Contions.

 

Replacement Process and Information

Please use the following information to replace MX OPC Server with DeviceXPlorer OPC Server.

Note

Import can be performed on Device Settings, Group Settings, and Tag Settings.
Port Setting will be created with the default value, so set the port before communicating.

Machine Series to be Replaced

* You can scroll this table sideways.

MELSOFT MX OPC Server DA / UA *1 DeviceXPlorer OPC Server 
MX Device
MX Device(Ver.2)
MELSEC Ethernet
MELSEC EZSocket *2

*1 Replacement is possible with MX OPC Server DA Ver 7.05 or MX OPC Server UA Ver 3.06 and later.
*2 EZSocket cannot be connected on 64-bit applications.

Replacement Data Types

* You can scroll this table sideways.

Item MELSOFT MX
OPC Server DA
MELSOFT MX
OPC Server UA
DeviceXPlorer OPC Server
BOOL
INT (SHORT)
UINT (USHORT)
WORD (USHORT)
UCOUNTER  〇 *1
UTIMER  〇 *1
URTIMER  〇 *1
UDINT 
DWORD (ULONG)
COUNTER 

× 〇 *2
TIMER  × 〇 *2
RTIMER  × 〇 *2
LTIMER  〇 *3
LRTIMER  〇 *3

LCOUNTER 

× 〇 *3
DINT (LONG)
LINT (LONGLONG) ×
ULINT (ULONGLONG) ×
REAL (FLOAT)
LREAL (DOUBLE)
STRING
WSTRING 
BOOL Array
INT Array
UINT Array 
WORD Array
UDINT Array
DWORD Array
LINT Array ×
ULINT Array ×
REAL Array
LREAL Array

*1 Configuration is output as USHORT.
*2 Converted to SHORT.
*3 Converted to ULONG.

Note

In MX OPC Server, the BOOL array tag is 1 bit per element.
(In DxpSERVER , BOOL array tag is 16 bits per element) When importing a BOOL array tag, convert it to cover all the devices with the BOOL type array tag set in MX OPC Server .

Example 1: MX OPC Server (before conversion): M7 Bool array size 15 Read range: M7 to M21 (15bit) DxpSERVER (after conversion): M0 Bool Array size 2 Read range: M0 to M32 (32bit)

Example 2: MX OPC Server (before conversion): D0.F Bool Array size 3 Read range: D0.F to D1.1 (3bit) DxpSERVER (after conversion): D0 Bool Array size 2 Read range: D0.0 to D1.F (32bit) 

Replacement Device Types

* You can scroll this table sideways.

Item MELSOFT MX
OPC Server DA
MELSOFT MX
OPC Server UA
DeviceXPlorer OPC Server
Link relay (B)
Counter coil (CC)
Counter present value (CN)
Counter contact (CS)
Data register (D)
Extended file register (ER) ×
GOT register (EG) ×
Annunciator (F)
Free run timer (FT) ×
Global label (GV)
Latch relay (L)
Long counter coil (LCC)
Long counter current value (LCN)
Long counter contact (LCS)
Long timer coil (LTC)
Long timer current value (LTN)
Long timer contact (LTS)
Long retentive timer coil (LTSC)
Long retentive timer current value (LSTN)
Long retentive timer contact (LSTS)
Internal relay (M)
File register (R)
Safety link relay (SA\B)
Safety counter control (SA\B)
Safety counter contact (SA\CS)
Safety counter presnet value (SA\CN)
Safety special register (SA\D) 
Safety data register (SA\D) ×
Safety internal relay (SA\M) 
Safety retentive timer coil (SA\STC)
Safety retentive timer contact (SA\STS)
Safety timer coil (SA\TC)
Safety timer present value (SA\TN)
Safety timer contact (SA\TS)
Safety link register (SA\W)
Safety input (SA\X)
Safety output (SA\Y)
Link special relay (SB)
Special register (SD)

Special relay (SM)
Link special register (SW)
Retentive timer coil (SC) 
Retentive timer present value (SN) 
Retentive timer contact (SS) 
Timer coil (TC)
Timer present value (TN)
Timer contact (TS)
Shared device (U3En\G)
Link register (W)
CC-Link input register (WR)
CC-Link output register (WW)
Input relay (X)
Output relay (Y)
Index register (Z)
File register (ZR)
Motion register (#)
Direct input (DX) × ×
Direct output (DY) × ×
Edge relay (V) × ×

Function Comparison

The following information compares the functions of MX OPC Server and DeviceXPlorer OPC Server.

General Specifications

* You can scroll this table sideways.

Item MELSOFT MX OPC Server DeviceXPlorer OPC Server
Maximum connected devices 10 255
Maximum tags 1,000,000 Unlimited
IoT interface Connectivity OPC UA Server
OPC DA Server
OPC XML DA Server ×
OPC AE Server
SuiteLink Server ×
DxpLink (HTTP Server) ×
MODBUS/TCP Server ×
MQTT Client ×
HTTP Client ×
Simulation function Increment
Sine
Square ×
Triangle ×
Step ×
Random ×
Shared Memory ×

Diagnostic function *1

×

Bridge function *2

×

Script function

×
Structure definition function
Scaling definition function
Linear
Square root
Power factor ×
Alarm definition function Level
Discrete
Ratio ×
Deviation ×
GX Works3 Global Label Import

*1 Monitor the device and system communication status in real time.
*2 Exchange data between multipe devices.

MELSEC Global Label Supported DataTypes

* You can scroll this table sideways.

MELSEC Data Type MELSOFT MX OPC Server DeviceXPlorer OPC Server
Scaler Bit
Word [Unsigned]/ Bit String [32-bit]
Word [Signed]
Double Word [Signed]
FLOAT [Single Precision]
FLOAT [Double Precision]
Time ×
String (32) × *1
String [Unicode] (32) ×
Pointer ×
Structured Data Type 〇 
Array Bit × *1
Word [Unsigned]/ Bit String [32-bit] × *1
Word [Signed] × *1
Double Word [Signed] × *1
FLOAT [Single Precision] × *1
FLOAT [Double Precision] × *1
Time ×
String (32) × *1
String [Unicode] (32) ×
Pointer ×
Structured Data Type 〇  × *1

*1 Data types to be supported in future versions.

 

OPC Interface Specifications

OPC DA

* You can scroll this table sideways.

Server Specification MELSOFT MX OPC Server DeviceXPlorer OPC Server
Supported version 3.0 3.0/2.05A
Prog.ID Mitsubishi.MXOPC.7 Takebishi.Dxp.7

OPC AE

* You can scroll this table sideways.

Server Specification MELSOFT MX OPC Server DeviceXPlorer OPC Server
Supported version 1.10 1.10
Prog.ID Mitsubishi.MXOPCAE Takebishi.DxpAe.7

OPC UA

* You can scroll this table sideways.

Server Specification MELSOFT MX OPC Server  DeviceXPlorer OPC Server
Supported version 1.04 1.04
EndPoint URL opc.tcp://[IP Address]:4841 opc.tcp://[IP Address]:52250
Data Access
Historian × 〇 
Alarm & Condition × 〇 
Method ×
Reverse Connect ×

 

* You can scroll this table sideways.

Security Policy MELSOFT MX OPC Server  DeviceXPlorer OPC Server 
None
Basic128Rsa15
Basic256
Basic256Sha256
Aes128Sha256RsaOaep  ×
Aes256Sha256RsaPss ×

* You can scroll this table sideways.

Security Mode MELSOFT MX OPC Server DeviceXPlorer OPC Server
None
Sign
SignAndEncrypt

Supported Machines

* You can scroll this table sideways.

Series MELSOFT MX
OPC Server DA
MELSOFT MX
OPC Server UA
DeviceXPlorer OPC Server
MITSUBISHI MELSEC
OMRON SYSMAC × ×
JTEKT TOYOPUC × ×
YOKOGAWA FA-M3 × ×
HITACHI HIDIC × ×
SHARP SATELLITE × ×
FUJI MICREX × ×
PANASONIC FP × ×
YASKAWA MP × ×
KEYENCE KV × ×
TOSHIBA PLC × ×
AZBIL CPL × ×
IAI CONTROLLER × ×
ROCKWELL AB × ×
SIEMENS SIMATIC × ×
GE PLC × ×
SAIA PLC × ×
LSIS XGT × ×

MODBUS 
FANUC CNC × ×
MITSUBISHI CNC × ×
MITSUBISHI EDM × ×
KAWASAKI ROBOT × ×
YASKAWA ROBOT × ×
YAMAHA ROBOT × ×
SHIBAURA MACHINE × ×
Sumitomo Heavy Industries - Molding Machine × ×
The Japan Steel Works - Molding Machine × ×
DPRNT  × ×
MTConnect  × ×
BACNet  × ×
EtherNet/IP  × ×
MITSUBISHI RFID × ×
OMRON RFID × ×
JCC AE sensor × ×
COGNEX BCR × ×
KEYENCE BCR × ×
MARS TOHKEN BCR × ×
MITSUBISHI ECO × ×
IEC61850 MMS Client × ×
IEC 60870-5-104  ×
DNP3 ×
OPC DA CLIENT × ×
OPC UA CLIENT × ×
OPC UA SUBSCRIBER × ×
ODBC CLIENT × ×
DDE CLIENT × ×
DxpLink CLIENT × ×
Modbus/TCP Server × ×
SHARED MEMORY × ×